Glossary Updates12 new terms added to the glossaries · October 2, 2026, 22:44 CEST
AI TechDocKnowledge

Glossary · Process instrumentation and analytical measurement

Intrinsically safe circuit

Also known as: IS circuit, Intrinsically safe loop

German: Eigensicherer Stromkreis

In explosion protection, an intrinsically safe circuit is a circuit in which any spark or thermal effect produced under the normal and specified fault conditions is incapable of causing ignition of a given explosive atmosphere.

  • Process instrumentation
  • Standards
  • Process industry

In one sentence

An intrinsically safe circuit cannot ignite a given explosive atmosphere by sparks or heat, even under specified fault conditions.

Example

The loop from an isolating barrier in the safe area to a temperature transmitter in zone 1, including the cable, forms one intrinsically safe circuit.

How it applies

  • Engineering: Verify each circuit: the associated apparatus's output parameters must not exceed the field device's input parameters, and the cable capacitance and inductance must stay within the permitted values.
  • Installation: Keep intrinsically safe circuits separated from non-intrinsically safe circuits in cabinets, cable trays and terminals, and mark them.
  • Maintenance: Modifications, such as a different cable length or replacement devices with other parameters, require re-verification.
  • Documentation: Document each circuit's verification with the devices, parameters and cable data. Loop diagrams and terminal plans should identify intrinsically safe circuits unambiguously.

Intrinsically safe circuit vs. intrinsically safe device

A device can be certified for use in intrinsically safe circuits, but the circuit is only intrinsically safe when the combination of all devices and cables has been verified.

By knowledge.aitechdoc.world · Published September 26, 2026 · Last reviewed

Source: IEC 60079-11, Explosive atmospheres — Part 11: Equipment protection by intrinsic safety "i"

Definitions follow the cited standards and specifications. Where a source is a copyrighted publication, such as an ISO, IEC or EN standard, the definition is a close paraphrase, not a verbatim quotation, so as not to infringe copyright. We recommend reading the original publication. The sections “How it applies” are editorial commentary by AI TechDoc Knowledge and are not part of any standard.